Made in Germany seal
  1. Home / 
  2. Products / 
  3. Fire safety / 
  4. SHEV / 
  5. Glass Skylight SHEV

Effective.
High-quality.
Durable.

Fire safety

  • Natural smoke and heat exhaust device in accordance with DIN EN 12101-2
  • Reliable opening to 165° in less than 60 seconds
  • Safety ensured by non-flammable, rigid roofing
Multiple LAMILUX Glass Skylight FE RWA installed on an industrial flat roof with partially opened glazing

DIN EN 12101-2

  • Reliable operation even after 1,000 activations (Re1000) and 10,000 ventilation cycles
  • Tested to trigger under snow loads of up to 200 kg (SL 1000 – SL 2000)
  • Tested reliability at outdoor temperatures as low as -15 °C
  • Fire protection under wind loads of up to 1,500 N/m²
  • Tested performance at ambient temperatures of 300 °C
Interior view of a LAMILUX Glass Skylight FE SHEV with opened glazing, visible drive mechanism and a view of the sky

Energy efficiency

  • Prevention of heat loss through a thermal bridge-free design
  • Full-surface thermally insulated GRP upstand with a U-value < 0.9 W/(m²K)
  • Smooth isotherm curve without kinks thanks to a thermoactive design
Closed LAMILUX Glass Skylight FE RWA installed on a gravel flat roof with insulated upstand and integrated glazing

Design

  • Custom sizes up to 150 x 300 cm
  • Flexible glazing options with U-values up to 0.6 W/(m²K)
  • Variants available with 0° and 3° inclinations
Opened LAMILUX Glass Skylight FE RWA installed on an industrial flat roof with visible drive mechanism and rectangular upstand

Application

  • Simple, efficient assembly of the prefabricated roof light
  • Multi-stage ventilation function for everyday use
  • Easy maintenance and permanent fall-through proofing
Multiple opened LAMILUX Glass Skylight FE RWA installed in rows on an industrial flat roof for smoke and heat exhaust

Dimensions and specifications of the Smoke Lift Glass Skylight FE

Order Dimensions (cm)
0° / 3°
Aa values (m²) for inclined upstandAa values (m²) steep-angle top ring with spoiler
 Aa value (m²) [24V] [48V] - soloAa value (m²) [24V] [48V] - tandemAa value (m²) [24V] [48V] - soloAa value (m²) [24V] [48V] - tandem
100/1000.60---
100/1500.90-1.08-
100/2001.24---
100/240-1.44--
100/250-1.53--
100/300-1.83--
120/1200.88-1.02-
120/1501.12---
120/1801.361.30--
120/240-1.79--
120/250-1.86--
120/300-2.23--
125/1250.97---
125/250-1.94--
140/1401.221.18--
150/1501.421.351.621.58
150/180-1.65--
150/200-1.86--
150/210-1.98--
150/240-2.27--
150/250-2.36--
150/300-2.84--

Interior view of multiple opened LAMILUX Glass Skylight FE RWA with visible supporting structure and view to the sky

Elegant smoke-exhaust window for greater safety

The Smoke Lift Glass Skylight FE combines a modern, flush-mounted design with the functions of a natural smoke and heat exhaust system in accordance with EN 12101-2. It ensures maximum daylight utilization in everyday use, excellent thermal insulation thanks to double- or triple-pane insulated glazing, and a reliable ventilation function. In the event of a fire, the window opens automatically and effectively leads smoke and heat to the outside, ensuring safe escape and rescue routes.

Thanks to its elegant aluminum frame, customizable color options, and fully integrated control technology, the Glass Skylight FE not only blends elegantly into any roof as a SHEV but also offers long-lasting quality and tested functional reliability. It thus combines architectural requirements with the highest level of fire protection without compromise.

Learn more about the Glass Skylight FE

EN 12101-2

Certified Smoke and Heat Exhaust System

The LAMILUX Smoke Lift Glass Skylight FE has been tested and approved in accordance with applicable European standards. These standards define all requirements for natural smoke and heat exhaust devices from operational safety and snow and wind load capacity to temperature resistance and fire resistance.

Smoke Lift Glass Skylight FE

In an emergency, every second counts: The LAMILUX Smoke Lift Glass Skylight FE opens automatically and vents smoke and heat to the outside in a controlled manner. This creates low-smoke layers that secure escape and rescue routes and buy valuable time for emergency responders. As a smoke-exhaust window, it meets all requirements for a reliable smoke and heat exhaust device and combines this safety feature with modern architecture, excellent thermal insulation, and an elegant daylighting solution.

Documents and downloads

Intended use of daylight systems

Instructions for use

cz, dk, en-us-gb, es, fi, fr, gb, hu, it, nl, no, pl, ro, se, tr

LAMILUX Smoke Lift EJ Glass Skylight FE

cn, cz, dk, en-us-gb, es, fi, fr, hu, it, jp, nl, no, pl, ro, ru, se, tr

Skylights

Product brochure

en-us-gb

Smoke and heat exhaust systems

Brochure

en-us-gb