Made in Germany seal
  1. Home / 
  2. Products / 
  3. Fire safety / 
  4. SHEV / 
  5. Glass Skylight F100 SHEV

Reliable.
Durable.
Modern.

Fire safety

  • Natural smoke and heat exhaust device in accordance with EN 12101-2
  • Opens quickly to 165° in less than 60 seconds
  • Ideal for use with non-flammable, rigid roofing materials
Interior view of a LAMILUX Glass Skylight F100 RWA with transparent glazing

DIN EN 12101-2

  • Operational reliability even after 1,000 activations (Re1000) and 10,000 ventilation cycles
  • Tested to activate under snow loads of up to 200 kg (SL 1000–SL 2000)
  • Tested reliability at outdoor temperatures as low as -15 °C
  • Fire protection under wind loads of up to 1,500 N/m²
  • Tested performance at ambient temperatures of 300 °C
Interior view of an industrial hall featuring a LAMILUX Glass Skylight F100 RWA as a central roof skylight for natural daylight and smoke and heat exhaust

Energy efficiency

  • Prevention of Heat Loss Through a Thermal Bridge-Free Design
  • Optimal U-values of 1.45–1.07 W/(m²K) according to EN ISO 10077-1
  • Optimized isotherm curves for continuous thermal insulation zones
Multiple LAMILUX Glass Skylight F100 RWA installed in a row on an industrial flat roof for natural daylight and smoke and heat exhaust

Design

  • Width of selection of sizes up to 150 x 150 cm
  • Variety of glazing options with U-values up to 0.95 W/(m²K)
  • Thermally insulated upstand in heights of 30, 40, and 50 cm
LAMILUX Glass Skylight F100 RWA installed on a gravel flat roof with transparent glazing and integrated drive system for smoke and heat exhaust

Application

  • Easy assembly on a flat roof
  • Standard ventilation function for everyday use
  • Permanent fall-through proofing and ease of maintenance
Interior view of a production hall with multiple LAMILUX Glass Skylight F100 RWA integrated into the ceiling

Dimensions and specifications of the Smoke Lift Glass Skylight F100

Order Dimensions (cm)Aa values (m²) for inclined upstandAa values (m²) Steep-slope top ring with spoiler
 24V / 48V - solo24V / 48V - tandem24V / 48V24V / 48V - tandem
100/1000.60---
100/1500.90-1.08-
120/1200.88-1.02-
120/1501.12---
125/1250.97---
140/1401.22---
150/1501.421.351.621.58

Detail view of a LAMILUX Glass Skylight F100 RWA installed on a gravel flat roof with transparent glazing and visible drive mechanism

Leading technology for enhanced fire safety

The LAMILUX Smoke Lift Glass Skylight F100 combines cutting-edge technology with the highest levels of safety and energy efficiency. Thanks to the integration of triple-pane insulated glazing with excellent U-values and balloon-style double seals, this smoke-exhaust window delivers outstanding airtightness. The fully thermally insulated, seamless GRP upstand is vapor-tight and ensures long-term, reliable thermal insulation.

Optimized profiles also ensure very high load-bearing capacity, while the UV-resistant edge seal provides long-lasting stability. The design, featuring smooth transitions between the glazing and the frame profile, allows for unobstructed rainwater runoff without any edges that trap dirt. Furthermore, the Glass Skylight F100 complies with DIN 18234 without requiring any additional measures, making it ideally equipped in terms of fire protection as well.

Learn more about the Glass Skylight F100

DIN EN 12101-2

Tested Smoke and Heat Exhaust Device

The LAMILUX smoke lift is tested and certified in accordance with European standards. These standards specify all requirements for natural smoke and heat exhaust systems from operational safety to snow load and wind load, as well as temperature and fire resistance. This ensures reliable performance even under extreme conditions.

LAMILUX Smoke Lift Glass Skylight F100

The Glass Skylight F100 combines the functions of an energy-efficient roof light with reliable smoke and heat exhaust capabilities in accordance with DIN EN 12101-2. It ensures safe smoke extraction in the event of a fire and provides natural lighting and ventilation in everyday use, a high-performance solution for modern fire protection concepts.

Documents and downloads

Glass Skylight F100

BIM Download

cz, en-us-gb, fr, nl, pl, ru

Intended use of daylight systems

Instructions for use

cz, dk, en-us-gb, es, fi, fr, gb, hu, it, nl, no, pl, ro, se, tr

LAMILUX Smoke Lift Glass Skylight F100

Assembly instruction

cn, cz, dk, en-us-gb, es, fi, fr, hu, it, jp, nl, no, pl, ro, ru, se, tr

Skylights

Product brochure

en-us-gb

Smoke and heat exhaust systems

Brochure

en-us-gb